Bilgi Arama
Belgeyi İndir () / 20
Zor İşler Bizimle Kolay

197517
Model Kodu: EASY-E4-DC-4PE1P

Eaton Moeller® series EASY I/O expansion for easyE4 with temperature detection Pt100, Pt1000 or Ni1000, 24 VDC, analog inputs: 4, push-in

General specifications

Product Name
Eaton Moeller® series EASY I/O expansion
Catalog Number
197517
EAN
4015081940950
Product Length/Depth
58 mm
Product Height
90 mm
Product Width
36 mm
Product Weight
0.1 kg
Certifications
UL Listed
UL Category Control No.: NRAQ, NRAQ7
IEC/EN 61000-4-2
IEC/EN 61131-2
IEC 60068-2-6
IEC 60068-2-30
IEC 60068-2-27
EN 61010
IEC/EN 61000-6-3
IEC/EN 61000-6-2
EN 50178
UL File No.: E205091
DNV GL
CE
UL hazardous location group D (propane)
UL hazardous location class I
UL hazardous location group B (hydrogen)
UL hazardous location group A (acetylene)
UL hazardous location group C (ethylene)
UL hazardous location division 2
Model Code
EASY-E4-DC-4PE1P

Ambient conditions, mechanical

Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
Horizontal
Vertical
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
57 - 150 Hz, 2 g constant acceleration
10 - 57 Hz, 0.15 mm constant amplitude
According to IEC/EN 60068-2-6

Cable

Cable length
≤ 30 m, unscreened, Analog inputs temperature resistance Pt100 or Ni1000 sensors

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - max
55 °C
Ambient storage temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - min
-40 °C
Environmental conditions
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Relative humidity
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)

Communication

Connection type
Push in terminals

Design verification

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Static heat dissipation, non-current-dependent Pvs
1 W

Electrical rating

Power consumption
1 W
Power loss
1 W
Rated operational voltage
20.4 - 28.8 V DC
20.4 - 28.8 V DC (Transistor outputs)
24 V DC (-15 %/+ 20 % - power supply)
24 V DC (transistor outputs)
24 V DC (digital inputs)
Supply voltage at DC - max
28.8 VDC
Supply voltage at DC - min
20.4 VDC

Electro magnetic compatibility

Air discharge
8 kV
Burst impulse
2 kV, Signal cable
2 kV, Supply cable
According to IEC/EN 61000-4-4
Contact discharge
6 kV
Electromagnetic fields
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 61000-6-3)
Surge rating
0.5 kV, Supply cables, symmetrical, EASY…DC, power pulses (Surge), EMC
1 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5 Level 4
Voltage dips
≤ 10 ms, Bridging voltage dips

Features & functions

Functions
Card diagnostic
Diagnostics below lower measurement range

General information

Degree of protection
IP20
Insulation resistance
According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Mounting method
Rail mounting possible
Overvoltage category
III
Pollution degree
2
Product category
Control relays easyE4
Protocol
MODBUS
Residual ripple
5 % (transistor outputs)
≤ 5 %
Resolution
12 Bit (0- 4095, digital, scaling per sensor)
Software
EASYSOFT-SWLIC/easySoft
Type
easyE4 extension
Used with
easyE4
Voltage type
DC

Input/Output

Input
Input type resistance sensor: Platinum sensor Pt100 (according to DIN EN 60751, IEC 751)
Input type resistance sensor: Nickel sensor Ni1000 (according to DIN 43760)
Input current
40 mA
Number of inputs (analog)
4
Number of inputs (digital)
0
Number of outputs (analog)
0
Number of outputs (digital)
0

Safety

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Between Analog inputs PT100 or Ni1000 and Power supply: no
Between Analog inputs and Power supply: no
Protection against polarity reversal
Yes

Short-circuit rating

Short-circuit protection
≥ 1A (T), Fuse, Power supply

Terminal capacities

Terminal capacity
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule